CMS DN 15 Pressure Valve

CMS pressure valves are angled pressure regulating valves with adjustable opening pressure and covering the differential pressure range (∆P): 2-8 bar (29-116 psi). The valve can be closed manually. The valves are specifically designed to prevent fluctuation due to low speed and/or low density. The pressure valve combines the functions of a pressure regulating valve, check valve and cut-off valve.

All valves are leak tightness tested. It is recommended to use the valve only in closed circuits. Please contact CMS Valve for more information.

PRODUCT DESCRIPTION CMS DN 15 Pressure Valve
WEIGHT (kg) 1,530 kg
BODY MATERIAL Steel forged
COLOR Golden Yellow
INPUT-OUTPUT CONNECTION SIZE (mm / inches) 15mm - 1/2 inches
MAXIMUM WORKING PRESSURE (bar - psig) 40 bar - 580 psig
OPERATING TEMPERATURE RANGE [°C]-[°F] -50 / +150°C (-58 /+302°F)
DIRECTION Angle
  • Applies to HCFC, HFC, R717 (ammonia) and R744 (CO₂).
  • Made of special, cold-resistant steel.
  • The shaft is made of polished stainless steel.
  • The valve is designed to withstand high internal pressure.
  • The valve must be mounted so that the stem is in a vertically upward or horizontal position.
  • Valves must be opened manually. The valve is designed to withstand high internal pressure. However, the piping system must be designed to reduce the risk of hydraulic pressure caused by thermal expansion.
  • When making valve connections, suitable welding methods should be used with materials compatible with the valve body. After welding is complete and before the valve is fully assembled, clean the valve internally to remove welding residues.
  • Be careful not to damage the Teflon conical ring.
  • The valve housing must be free from stresses (external loads) after installation.
  • The outer surface of the valve housing must be protected against corrosion with a suitable protective coating after installation and assembly.
  • Check that the shaft is free from scratches and impact marks.
  • If the Teflon cone ring is damaged, the entire cone assembly must be replaced.

Use only genuine CMS Valve parts, including gaskets, to replace valve parts. In case of hesitation, please contact CMS Valve. CMS Valve accepts no responsibility for errors and omissions. CMS Valve reserves the right to make changes to products and specifications without prior notice.